8-4
Communicating with Devices on an DeviceNet Link
2.
The software then prompts you to either upload or download. Choose upload. RSNetWorx will then browse the network and
obtain their settings.
3.
Right click on the 1769-ADN and choose Properties.
4.
Click on the I/O Bank 1 Configuration tab, then choose upload when prompted. The actual 1769-ADN I/O layout appears.
From this screen you can configure the I/O modules in the 1769-ADN system by simply clicking on the slot number box
associated with each I/O module.
5.
When the I/O modules are configured, click on the Summary tab. Note the number of bytes of input and output data. This
will be used later when adding the adapter to the 1769-SDN’s scanlist.
6.
Click Apply, then OK to save the configuration and download it to the adapter.