ELECTRIC INSTALLER section
Ed. 06/2014 – FW version
1.002
37
1. Set up orange CAN-BUS connector after removing it from its packaging.
2. Cut a cable section of measure allowing installation without any sharp bending.
3. Select a cable section end, remove sheath for about 70-80 mm, carefully preventing
any cut on shield (braiding and/or aluminium sheet and, if any, naked connector in
contact with braiding) and wires inside.
4. Wind shield and connect it to a 4-mm eyelet, as shown in Figure 17, Page 35, details
C and D. Then, act as follows:
5. Connect three coloured wires to "P8" orange connector, following scheme in Figure
19, Page 36.
Comply with proper indications L, H, GND shown in Table 8, Page 34, Figure 19 and
DDC board on the basis of "P8" connector.
- If DDC is an
intermediate note
on network (see Figure 15/Page 34): also perform
point 7;
- If DDC is a
final node
on network, do not perform point 7 and directly go to point 8.
6.
For intermediate nodes only
: Repeat operations in points 1 to 4 for the other CAN
BUS section end necessary. Also follow point 5, but refer to Figure 18, Page 36 for
connecting cable to "P8" connector. Then, go to point 8.
7. Insert "P8" orange connector with wires before opening set up on DDC cover, then in
the relevant DDC socket, carefully checking it is properly inserted.
8. Use rear cover fastening screw located close to CAN BUS socket to fasten eyelet (or
two 4-mm eyelets) (detail D, Figure 17 Page 35).
Summary of Contents for Roburbox100
Page 1: ...Roburbox100 Plant Control Interface Installation and use manual ...
Page 6: ...RB100 Installation and Use Manual IV Ed 06 2014 FW version 1 002 ...
Page 8: ...RB100 Installation and Use Manual 2 Ed 06 2014 FW version 1 002 ...
Page 28: ...RB100 Installation and Use Manual 22 Ed 06 2014 FW version 1 002 ...
Page 50: ...RB100 Installation and Use Manual 44 Ed 06 2014 FW version 1 002 ...
Page 68: ...RB100 Installation and Use Manual 62 Ed 06 2014 FW version 1 002 ...
Page 83: ......