ELECTRIC INSTALLER section
Ed. 06/2014 – FW version
1.002
29
2.4 ELECTRIC CONNECTIONS FOR VALVE SERVICE
Outputs
- The valve control output is composed of a free (NO/NC) diverter contact:
o
the NO contact is closed when the system requires that the position of the
valve is towards the heating side or towards the separable group;
o
the NC contact is closed when the system requires that the position of the
valve is towards the cooling side or towards the basic group;
- the output control relay is of toggle type (in case of power cut to the appliance, the
contact remains in the original position);
- the maximum applicable voltage is 250 Vac;
- the maximum applicable current is:
o
resistive loads: 4A;
o
inductive loads: 3A;
- cable maximum length is 300 metres.
Inputs
There are two digital inputs for the management of auxiliary limit switch contacts, if any.
Maximum allowable length of connection cables for inputs:
Max Resistance for On [
Ω
]
Max Resistance for Off [k
Ω
]
Max cable length (m)
200 [
Ω
] 50
[k
Ω
] 300
(m)
Digital input cable must be shielded by grounded screen on each end.
Summary of Contents for Roburbox100
Page 1: ...Roburbox100 Plant Control Interface Installation and use manual ...
Page 6: ...RB100 Installation and Use Manual IV Ed 06 2014 FW version 1 002 ...
Page 8: ...RB100 Installation and Use Manual 2 Ed 06 2014 FW version 1 002 ...
Page 28: ...RB100 Installation and Use Manual 22 Ed 06 2014 FW version 1 002 ...
Page 50: ...RB100 Installation and Use Manual 44 Ed 06 2014 FW version 1 002 ...
Page 68: ...RB100 Installation and Use Manual 62 Ed 06 2014 FW version 1 002 ...
Page 83: ......