GENERAL AND TECHNICAL FEATURES section
Ed. 06/2014 – FW version
1.002
11
Operation of inputs for request services
One of the following types apply to each request service used:
Analogue input:
this configuration allows receiving a 0-10 Volt input signal. RB100
interface sends to Direct Digital Controller a setpoint request proportional with input
voltage. Thus, setpoint is provided for by RB100.
Digital input with local setpoint:
this configuration allows receiving an input digital signal
(clean contact). When received on input, RB100 sends to Direct Digital Controller a
setpoint request with a well-defined value, previously set in a proper interface parameter.
Digital input with remote setpoint:
this configuration allows receiving an input digital
signal (clean contact). When received on input, RB100 only sends to Direct Digital
Controller a turning-on request; the setpoint value to be used by DDC to meet such
request is set on DDC itself [ref. to DDC Use and Programming Manual (D-LBR 249)].