4 Operation
MANUAL TME400-VCF · EN04 · 2019 March 26th
54
4.2. Programming
There are five buttons available on the front foil for programming of the TME400. Al-
ternatively, you can carry out programming via the RMGView
EVC
operating software
(see
chapter 4.4 RMGViewEVC
).
4.2.1.
Programming with the programming buttons
Basically, you proceed as follows for the programming:
•
First check the protection status of the coordinate. When parameters are not
protected, you can carry out changes, as described below without additional
measures.
•
With parameters protected by code word, you must enter it first in coordinate
Z15. Please read how to make the entry as below.
•
With parameters protected for custody-transfer applications, you must press
the calibration button first.
Caution
It is necessary to remove the seals, particularly the seal over the calibration
button in order to press the calibration button (see Figure 9: Position of the
calibration button).
The TME400 must only be used for custody transfer with unbroken seal. Re-
moval or damage to seals normally entails considerable expenses!
Re-application of seals must only be carried out by an officially recognized
inspection authority or calibration officials!
The principle of the programming is shown based on the example of changing the
output pulse factor:
I.
Move with the arrows (
) to the position: A11
II.
Activate the calibration button (see
Figure 9: Position of the calibration button
)
III.
The blinking "INPUT" text appears above the displayed value in the display
view.
IV.
Press
for more than 2 seconds
V.
The value begins to blink at a position