66
Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
Fig. 59:
Setup screen for operation parameters - "Automatic Mode"
Fig. 59 shows the setup screen for the operating parameters of the Liquid Coo-
ling Package Plus for the functions in automatic mode. The following are para-
meters that are displayed or settings that may be made on this screen:
Displays
Explanation
Operating
mode
Selection of the Liquid Cooling Package Plus operating mode.
Here, automatic mode is selected.
Automatic
mode
Pull-down menu for setting the control of the fans and the control
valve of the Liquid Cooling Package Plus.
Fig. 60:
Setting options
- Full:
In this mode, the fan speed and the position of the control valve
are controlled automatically.
- Fan only:
In this mode, only the fan speed is controlled automatically. The
position of the control valve can be set to a fixed position using
the function for manual operation. This position is saved and used
again after the system is restarted.
- Valve only:
In this mode, only the position of the control valve is controlled au-
tomatically. The fan speed can be set to a fixed speed using the
function for manual operation. This speed is saved and used
again after the system is restarted.