Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
6
Installation – "Getting
Started"
6.1
Installation conditions
In order to ensure problem-free operation of the Liquid Cooling Package Plus,
the following conditions for the installation location should be observed:
Supply connections required at the installation site
Tab. 3:
Supply connections required at the installation site
Floor conditions
- The floor of the installation space should be rigid and level.
- Choose the installation site so that the unit is not situated on a step, unlevel
location, etc.
Climatic conditions
- The room temperature must be b6 °C and +40 °C
- The relative air humidity must be below 80%.
Electromagnetic interference
- Interfering electrical installations (high frequency) should be avoided.
Type of connection
Connection description:
Power connection:
- 230 V 50/60 Hz
with connection cable DK 7856.026
16 A, 1~, CEE connector, 3-pole
- 400 V, 3~, N, PE, 50/60 Hz
with connection cable DK 7856.025
16 A, 3~, CEE connector, 5-pole
Cooling water connection:
- +6 °C to +20 °C inlet temperature
- 5 bar permissible operating pressure
- Volumetric flow: depending on design
(cf. Chapter 6.5.1, "Cooling output")
- 1" threaded pipe connection
Note:
Please see the notes and data regarding the cold water connection in
Chapter 6.4.2, "Cooling water connection" and in Chapter 14.1, "Hydrologi-
cal information".
Recommendation:
To keep the Liquid Cooling Package Plus easy to service, maintain a dis-
tance of min. 1 m between the front and rear of the device and the nearest
wall.
Recommendation:
Room tempe 22 °C at 50% relative air humidity, according to ASH-
RAE guidelines.