68
Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
Fig. 62:
Setup screen for operation parameters - "Manual Mode"
Fig. 62 shows the setup screen for the operating parameters of the Liquid Coo-
ling Package Plus for the functions in manual mode.
The following are parameters that are displayed or settings that may be made
on this screen in addition to the functions in automatic mode:
Tab. 12: Operating parameters for manual mode
Setpoints
Explanation
Operating
mode
Selection of the Liquid Cooling Package Plus operating mode.
Here, manual mode is selected.
Fanspeed
Fan speed setting (0 = off / 1 to 4 = speed 1 to 4).
The last setting that was made is saved and used again after the
system is restarted if the setting "Valve only" is selected in auto-
matic mode. Otherwise, the fan modules are controlled automati-
cally.
Enable fans
Switch off individual fan modules for testing.
This function is only possible in manual mode. In automatic mode,
all fan modules are activated.
Valve
Setting of the opening position of the control valve. This is set as a
percentage [%] between 0 and 100%.
The last setting that was made is saved and used again after the
system is restarted if the setting value "Fan only" is selected in
automatic mode. Otherwise, the control valve is controlled auto-
matically.
Note:
After the Liquid Cooling Package Plus is connected to the mains or restar-
ted, the controller is always in automatic mode.