30
Operating and Maintenance Instructions – 6 Installation – "Getting Started"
Rittal Liquid Cooling Package Plus
Fig. 20:
Placement of foam strips for devices with sideways air throughput - top view
1
Liquid Cooling Package Plus
2
Server enclosure
3
Foam strips on warm air side
4
Foam strips on cold air side
5
Area in which the foam strips can be positioned
• If there is any remaining length of the foam strip on the server rack, cut it off
at the top edge of the rack.
• On the side of the server enclosure opposite the Liquid Cooling Packing Plus,
mount a side panel on the two side panel mountings. Align it with the front and
rear side of the enclosure.
• Using the 8 assembly screws, screw the side panel firmly onto the side panel
holders and the side panel mounting brackets.
• Seal off any cable entries which may be present with corresponding brush
strips or similar.
Dismantle the server enclosure door
Before baying a Liquid Cooling Package Plus, one or both of the server enclo-
sure doors must be dismantled so that the attachment points for the baying
connectors are accessible and are not covered by a door edge.
2
3
5
4
5
1
Note:
The Liquid Cooling Package Plus can, as desired, be bayed onto a server
enclosure with a width of either 600 mm or 800 mm. Thus, the Liquid Cooling
Package Plus accessories include a total of four foam strips with differing di-
mensions.
The foam strips for a 600 mm wide server enclosure may be ordered with the
following numbers from the Rittal accessory range:
- Model No. SK 3301.370 for the LCP side
- Model No. SK 3301.380 for the side with the side panel
The foam strips for a 800 mm wide server enclosure may be ordered with the
following numbers from the Rittal accessory range:
- Model No. SK 3301.320 for the LCP side
- Model No. SK 3301.390 for the side with the side panel