85
1. P1 (4-Pin), P2 (7-Pin) and P5 (5-Pin) - Low-Voltage
Internal Wiring
Connections – Connect main twist-
lock wire harness to these connections. Pre-wired
from the factory.
2. RJ-14 CONNECTOR (J1)
This connector is used to program the furnace control
at the factory. It should never be connected to a tele-
phone line or a telephone. Doing so could damage the
furnace control or the telephone (or telephone lines)
or both.
3. SPARK IGNITION TRANSFORMER (T1)
The spark ignition transformer resides on the furnace
control. The transformer provides spark energy at ap-
proximately 60 hz frequency and a minimum of 12KV.
4. BIAS / TERMINATION (S4)
For current installations, all three of the dip-
switches in bank SW4 must be in the “OFF” posi-
tion. If not, the system may not be able to
communicate.
5. COMMUNICATIONS LED’S (U38)
Two LED’s are provided to indicate the status of com-
munications. A red LED (Labeled TX) is provided for
transmit and a green LED (Labeled RX) is provided
for receive. These LED’s will be lit in an undefined
pattern when other communicating components are
attached and communicating with the furnace control.
6. LINE VOLTAGE CONNECTIONS (120VAC, L1)
Four ¼” Quick-Connect style terminals are provided
for internal connections and accessories.
7. INDUCED DRAFT MOTOR (INDUCER) OUTPUT
(P3)
This three-pin Mate-n-Lok style connector provides
power to both the high and low speed inducer outputs.
8. NEUTRAL TERMINALS (N)
Four ¼” Quick-Connect style terminals are provided
for internal connections and accessories.
9. ELECTRONIC AIR CLEANER (E.A.C.) OUTPUT (T3)
This output is used to energize an electronic air
cleaner. The output will provide 1.0 amp at 115 VAC.
This output is energized any time the blower motor is
above the airflow CFM values specified below. Airflow
below this value is not considered to be enough for a
typical electronic air cleaner to perform properly.
For ½ HP motors - Electronic air cleaner is energized
any time the blower is above 500 CFM
For ¾ HP motors - Electronic air cleaner is energized
any time the blower is above 600 CFM
For 1 HP motors - Electronic air cleaner is energized
any time the blower is above 700 CFM
Continuous fan speeds are selectable and some lower
fan speeds may not deliver enough airflow to operate
an electronic air cleaner. The IFC determines the mini-
mum airflow necessary to operate an electronic air
cleaner and will not turn on the electronic air cleaner
unless the airflow is high enough for the EAC.
10. HUMIDIFICATION (T3) AND DEHUMIDIFICATION
HUMIDIFIER – The humidifier contacts (labeled
“HUM” (2)) are “dry” contacts on the I.F.C. This means
that the terminals are connected directly to the con-
tacts of a board-mounted relay. The coil of the relay is
controlled by the microprocessor of the IFC. The coil
is engaged roughly any time the heat speed blower is
engaged and (1) 24VAC is present on the thermostat
terminal of the IFC labeled “HUM STAT” or (2) a com-
municating thermostat with humidification and dehu-
midification capability is installed with call for
humidification present. (See Figure 45 for location of
humidification/dehumidification inputs on furnace con-
trol.)
INTEGRATED FURNACE CONTROL
Co
m
m
un
ica
tin
g F
urn
ace
!
WARNING
DO NOT CONNECT A TELEPHONE OR PHONE LINE
TO THE CONNECTOR (JACK) AT POSITION J-11.
DOING SO COULD CAUSE IRREPARABLE DAMAGE
TO EITHER THE FURNACE CONTROL (I.F.C.) OR
THE TELEPHONE (OR TELEPHONE LINE) OR
BOTH.
FIGURE 45
ELECTRONIC AIR CLEANER AND HUMIDIFIER TERMINALS
ST-A1194-64-00
Summary of Contents for 96MDV Series
Page 34: ...Field Conversions 34...
Page 35: ...Field Conversions 35...
Page 36: ...36 Field Conversions...
Page 37: ...37 Field Conversions...
Page 38: ...Field Conversions 38...
Page 115: ...115 TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics...
Page 120: ...120 Diagnostics TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS...
Page 126: ...126 FIGURE 65 2 STAGE ECM FURNACE WIRING DIAGRAM Troubleshooting...
Page 127: ...127...
Page 128: ...128 CM 1015...