HIGH ALTITUDE
NATURAL GAS AT HIGH ALTITUDES
No high altitude pressure switch changes are required;
only a 4% derate at altitudes above 2,000 feet.
NATURAL GAS
NOTE:
Factory installed orifices are calculated and sized
based on a sea level Natural Gas heating value of 1100
BTU per cubic ft. Regional reduced heating values may
nullify the need to change orifices except at extreme alti-
tudes.
The following are examples of orifice sizing using the Na-
tional Fuel Gas Code Annex E, tables E.1.1(a) and
E.1.1(d). For a simplified estimation of orifice size based
on heating value and elevation, use Table 13. However,
calculations are the best method.
Example: 900 BTU/ft
3
Regional Natural Gas Heating
Value
I / H = Q
14000 / 900 = 15.56 ft.
3
I = Sea Level input (per burner): 14000
H = Sea Level Heating Value: 900
Q = 15.56 ft
3
Natural Gas per hour.
From Table E.1.1(a) of
National Fuel Gas Code Hand-
book,
current edition (3.5
w.c. column)
Orifice required at Sea Level: #49
From Table E.1.1(d) of
National Fuel Gas Code Hand-
book,
current edition
Orifice required at 5000 ft. elevation (4% de-rate per
thousand ft.): #51
Orifice required at 8000 ft. elevation (4% de-rate per
thousand ft.): #52
!
CAUTION
I
NSTALLATION OF THIS FURNACE AT ALTITUDES
ABOVE 2000 FT. (610 M) SHALL BE IN ACCOR-
DANCE WITH LOCAL CODES, OR IN THE AB-
SENCE OF LOCAL CODES, THE NATIONAL FUEL
GAS CODE, ANSI Z223.1/NFPA 54 OR IN CANADA,
NATURAL GAS AND PROPANE INSTALLATION
CODE, CSA B149.1.
!
CAUTION
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE
FURNACE INPUT RATING BE ADJUSTED AND THAT
THE SIZE OF THE BURNER ORIFICES BE RE-CAL-
CULATED BASED ON ELEVATION AND GAS HEAT-
ING VALUE. THE BURNER ORIFICES MAY (OR MAY
NOT) NEED TO BE CHANGED. THE FOLLOWING EX-
AMPLES SHOW HOW TO DETERMINE IF AN ORI-
FICE CHANGE WILL BE NECESSARY AND HOW TO
DETERMINE THE NEW ORIFICE SIZE.
IN CANADA, AS AN ALTERNATE TO ADJUSTING
THE BURNER ORIFICE SIZE, THE MANIFOLD GAS
PRESSURE MAY BE ADJUSTED. THIS METHOD IS
COVERED LATER IN THIS SECTION. THIS METHOD
OF ADJUSTING MANIFOLD PRESSURE MAY ONLY
BE USED IN CANADIAN INSTALLATIONS.
Summary of Contents for 96MDV Series
Page 34: ...Field Conversions 34...
Page 35: ...Field Conversions 35...
Page 36: ...36 Field Conversions...
Page 37: ...37 Field Conversions...
Page 38: ...Field Conversions 38...
Page 115: ...115 TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics...
Page 120: ...120 Diagnostics TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS...
Page 126: ...126 FIGURE 65 2 STAGE ECM FURNACE WIRING DIAGRAM Troubleshooting...
Page 127: ...127...
Page 128: ...128 CM 1015...