Condensate water drain
The condensate water drain is
located on the unit's base.
The condensate drain is connected
to the discharge nozzle supplied.
A solid or flexible 3/4” discharge
connector can be installed on this.
■
The discharge hose must always
be laid at an incline of at least
2 % so that the water can flow
unhindered from the drip tray.
■
Alternatively, a condensate
pump can be fitted to the unit in
order to pump the condensate
water to a drainage point
located at a higher level.
■
If drainage is to be carried out
through the wall, the relevant
measures such as holes for
correct condensate drainage
must be taken before installing
the unit.
■
See the diagram at the side for
information on the location of
the drainage connection.
All measurements in mm
Location of the condensate drain
56
430
Putting the panel on
The unit is supplied from the
factory with a separate panel.
This must therefore be put on
properly before starting the unit.
Follow one of the following two
instructions depending on the unit
equipment.
Installing the SLE panel
without LED light function
To equip the unit with the panel,
follow these instructions.
1. Open the connection flap on
the bottom.
2. Guide the power cable through
the cable gland and then onwards
to the terminal block.
3. Then attach the cable for the
power supply. Connect the L1
phase accordingly to the first
grey terminal (L1) from the left.
Connect the zero phase N to the
first blue terminal (N) from the left
and connect the earth conductor
PE to the earth conductor terminal
(PE) (also see the electrical wiring
diagram).
4. Re-close and fasten the
connection flap.
5. Connect the unit to the power
supply.
6. Remove the control board cover.
7. Set the room humidity on the
control board (see commissioning).
8. Re-attach the control board
cover using the two screws.
9. Hang the SLE panel into the top
edge, use the top guide pins to
centre it and then let it rest gently.
10. Push the panel using the
bottom guide pins.
11. Tighten the two locks
clockwise so that the bottom of
the panel can no longer be lifted.
9