Register
Byte
Database
parameters
Min Max
Hr.
Description
8
14
Cond_temp1
(decimal)
-40
100
0
Condenser temperature:
Use as described above
15
Cond_temp1
(fraction)
-40
100
0
9
16
Aux_temp
(fraction)
-40
100
0
Auxiliary probe temperature:
Use as described above
17
Aux_temp
(fraction)
-40
100
0
10
18
Amb_temp
(decimal)
-40
100
0
Ambient air temperature:
Use as described above
19
Amb_temp
(fraction)
-40
100
0
11
20
Amb_hum
(High byte)
0
100
0
Ambient air humidity:
High byte is insignificant and always contains
zero. Only low byte can be used
21
Amb_hum
(Low byte)
12
22
RH_set
40
95
40
Humidity setpoint
23
RH_Fan
40
95
40
Humidity setpoint for extractor fan start
13
24
Temp_set
(decimal)
0
36
0
Temperature setpoint:
Used in the same way as Evap_temp1
25
Temp_set
(fraction)
16
30
Fail_start
0
1
0
Status of Fail_start mode
31
SB_mode
0
1
0
Standby mode status
17
32
DEH_mode
0
1
0
Dehumidification status
33
Ice_mode
0
1
0
Defrosting mode
18
34
LP_mode
0
1
0
LP fault mode status
35
Sens_mode
0
1
0
Sensor fault mode status
19
36
HP_mode
0
1
0
HP fault mode status
37
Amb_mode
0
1
0
Ambient fault mode status
20
38
AmbT_
mode
0
1
0
Ambient temperature fault mode status
39
AmbRH_
mode
0
1
0
Ambient humidity fault mode status
29