1. Level
2. Level
3. Level
°
CXX
External heating
EFXX
External fan
SIXX
Service interval
tESt
Self-test
rHXX
“Value”
"Value confirmed"
“Value confirmed”
“Value confirmed”
OK
“Value confirmed”
“Test confirmed”
“Value”
“Value”
“Value”
OK
OK
OK
OK
OK
OK
OK
OK
Menu structure of the SLE air dehumidifier
Menu items
Code: RH
The code “RH” stands for the
relative air humidity that the unit
should reach. The value can be set
between 40 and 99 % RH. The
default value is 60.
Code: EF
The code “EF” stands for external
heating control with the aim of
reaching the specified air humidity
more quickly. The set value may
differ from the setpoint humidity
so that the external heating can
either operate permanently or
merely provide a support function.
The value can be set between
40 and 99 % RH. The default
value is set to “OF”.
Code: SI
The code “SI” stands for the
maintenance interval that the
operator or fitter requires. This
value is indicated in weeks and can
be set from 01 to 99. The default
value is “OF.”
Code: tE
The code “tE” stands for testing
and the value “St” for self-test.
To start the self-test, press “OK”
and to cancel it, hold the down
key down for 5 seconds.
Menu structure
To define the setpoints using the
integrated operator panel, hold
down the “OK” key for 5 seconds
so that the display switches from
the humidity currently measured to
the menu item rHXX.
If you would like to exit the menu,
do not press any keys on the
operator panel for 10 seconds.
NOTE
The corresponding terminals
for these options are located
on the control board of the
unit.
Code: °C
The code “°C” stands for external
heating control with the aim of
reaching a defined setpoint. The
value can be set to between 05
and 34. This value is set to “OF”
by default.
OK
5 seconds
13