Register
Byte
Database
parameters
Min Max
Hr.
Description
21
40
SW build
number
(high)
0
65535
x
Software build number
41
SW build
number (low)
0
22
42
SW version
(Main version)
0
255
x
Main version number of the software
43
SW version
(Minor version)
0
255
x
Minor version number of the software
23
44
HP alarm
Temp.
(decimal)
0
99
60
HP faults occur when Cond_temp1 is greater than
this value.
Used in the same way as Evap_temp1
45
HP alarm
Temp.
(fraction)
41
80
Fan_function
0
1
0
Activate fan function in standby mode
81
42
82
Time_wait_
fan
60
7200 3600
Waiting time until fan starts up in standby mode,
if activated (seconds)
83
43
84
Time_run_
fan
15
600
60
Fan operating time in standby mode, if activated
(seconds)
85
44
86
RH_Fen
0
1
0
Activate/deactivate extractor fan function
87
Service_ena
0
1
0
Activate/deactivate maintenance interval function
45
88
Service_int
0
99
0
Maintenance interval value in weeks
89
30
REMKO SLE 45-85