94
Part V
Signals
Alarms.AlaAcknow
X,3
266
255
External alarms are acknowledged by
setting this signal to the alarm number
that you want to acknowledge
Alarms.AlaBlock
X,3
267
255
External alarms are blocked by setting
this signal to the alarm number that you
want to block
Alarms.AlaUnBlock
X,3
268
255
External alarms are unblocked by setting
this signal to the alarm number that you
want to unblock
QSystem.Sek
X,3
269
-
Real-time clock: Second 0-59
QSystem.Minute
X,3
270
-
Real-time clock: Minute 0-59
QSystem.Hour
X,3
271
-
Real-time clock: Hour 0-23
QSystem.WDay
X,3
272
-
Real-time clock: Weekday 1-7,
1=Monday
QSystem.Week
X,3
273
-
Real-time clock: Week number 1-53
QSystem.Date
X,3
274
-
Real-time clock: Day of the month 1-31
QSystem.Month
X,3
275
-
Real-time clock: Month 1-12
QSystem.Year
X,3
276
-
Real-time clock: Year 0-99
LonWorks network variables
Name
Type
Description
Configuration
nciSndHrtBt SNVT_time_sec
Pulse
(0=disabled)
nciRcvHrtBt
SNVT_time_sec
Max. time before a requested value is discarded
nciSetPnts SNVT_temp_setpt
Setpoints
nciHvacType SNVT_hvac_type
Model
nciBypassTime
SNVT_time_min
Time in bypass mode
nciCO2PresenceHyst SNVT_ppm
Hysteresis for inactivation of occupancy
nciCO2PresLimit SNVT_ppm
CO
2
concentration at which occupancy is activated
nciCO2LimitLow SNVT_ppm
CO
2
concentration at which the dampers start to open
nciCO2LimitHigh SNVT_ppm
CO
2
concentration at which the dampers are
completely open
nciPpmHyst SNVT_ppm
Hysteresis before ppm values are transmitted via the
bus
nciTempHyst SNVT_temp_p
Hysteresis before temperature values are transmitted
via the bus
nciPercentHyst SNVT_lev_percent
Hysteresis before percentages are transmitted via the
bus
Inputs (nvi)
nviSpaceTemp SNVT_temp_p
Room
temperature
nviSetPtOffset SNVT_temp_p
Setpoint
offset
nviOccManCmd SNVT_occupancy
Setting
of running mode, Occ/UnOcc/Byp/Standby
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...