32
Part II
Installation
24
DO6
Digital output 6, 24 V AC-output.
Thermal actuator, heating.
Wiring for 24 V AC-loads
:
24 V AC actuator is connected between terminal 24 and
terminal 23, GDO.
Alternatives:
-
Forced ventilation
- Thermal actuator, cooling
- Three-point actuator heating increase
- Three-point actuator heating decrease
- Three-point actuator cooling increase
- Three-point actuator cooling decrease
- Lighting control
- Blind in
- Blind out
- Sum alarm
- Sum alarm A
- Sum alarm B
25
DO7
Digital output 7, 24 V AC-output.
Thermal actuator, cooling.
Wiring for 24 V AC-loads
:
24 V AC actuator is connected between terminal 25 and
terminal 23, GDO.
Alternatives:
-
Forced ventilation
- Thermal actuator, heating
- Three-point actuator heating increase
- Three-point actuator heating decrease
- Three-point actuator cooling increase
- Three-point actuator cooling decrease
- Lighting control
- Blind in
- Blind out
- Sum alarm
- Sum alarm A
- Sum alarm B
26
GDO
24 V AC out for DO8.
Terminals 20, 23
and 26 are
connected
internally, max total
load 12 VA.