68
Part III
Configuration
The Select button
By pressing the Select button on RU-DOS, you move between the following indications:
Fan speed. When this symbol is lit you change the fan speed with the
INCREASE/DECREASE buttons.
Current setpoint in °C to one decimal point and 0.5°C resolution
Current outdoor temperature in °C to one decimal point and 0.1°C resolution
CO
2
: Current percentage of CO
2
0…9999 ppm
RH: Current humidity 0...100% RH
Lighting control: The lighting can be turned on/off with the
INCREASE/DECREASE buttons.
Control of blinds: The blinds can be controlled with the INCREASE/DECREASE
buttons. The output for opening the blinds is active as long as you are holding the
INCREASE button depressed, and the output for closing the blinds is active as long
as you are holding the DECREASE button depressed.
The parameter menu
In the RU-units with display it is possible to set different parameter values in a parameter
menu. The parameter menu is accessed by simultaneously holding the INCREASE and
DECREASE buttons depressed for about 5 seconds and then pressing the INCREASE button
twice. The Service indication will be displayed.
First the display will show the parameter-number 1. Scroll between parameters by using the
INCREASE and DECREASE buttons.
Press the Occupancy button to select the desired parameter. The parameter number will be
replaced by the parameter value. The value can be changed using the INCREASE and
DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly
and then with increasing speed in 3 - 4 steps with 2 - 3 seconds between steps.
Acknowledge/Regret
To acknowledge and store a set parameter value, press the Occupancy button again, the
display then returns to showing the parameter number. To retrieve the original value, i.e. the
value before change, press the INCREASE and DECREASE buttons at the same time. The
original value is shown on the display.
Return
After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are
pressed at the same time while in the menu, the display returns to the normal view. Exit is
shown on the display after the last parameter. The parameter menu is exited by pressing the
Occupancy button while in Exit. Pressing on INCREASE goes to the first parameter and
pressing on DECREASE goes to the last parameter.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter
number
Description
FS
1
Basic heating setpoint
22°C
2
Basic cooling setpoint
24°C
3
Neutral zone at Stand-by, Heating sp=Basic sp heating-3,
Cooling sp=Basic sp 3
3°C
4
Heating setpoint at Unoccupied
15°C
5
Cooling setpoint at Unoccupied
30°C
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...