Regio Manual Maxi
Chapter 4
Technical data
15
Min switching voltage ............................................................................................... 12 V AC
Max continuous current DO1-3 ................................................................... 4 A resistive load
Max continuous current Common, terminal 13 ........................................... 8 A resistive load
Max inrush current .......................................................................................................... 20 A
Min switching currenrt ................................................................................................. 10 mA
AC-connection
Max switching power, resistive load ........................................................................ 1000 VA
Insulation, coil-contact ........................................................................................... 4000 V
RMS
For more information about inputs and outputs, see the chapter
Wiring
.
RU
Supply voltage ..................................................................................................... Fed from RCP
Protection class .................................................................................................................. IP20
Weight ............................................................................................................................... 110 g
Max cable length between RU and RCP ............................................................................ 30 m
Dimensions
Models without setpoint knob ........................................................................ 95 x 95 x 28 mm
Models with setpoint knob ............................................................................. 95 x 95 x 31 mm
Built-in temperature sensor
Type ................................................................................................ NTC, linearised, 15 kOhm
Measuring range ........................................................................................................... 0...50°C
Accuracy ................................................................................................. +/-0.5°C at 15...30°C
RU with display
Display type ....................................................................... LCD with background illumination
Accessories for Regio Maxi
External temperature sensors ........................ TG-R5/PT1000,TG-UH/PT1000,TG-A1/PT1000
Occupancy detector ........................................................................................................ IR24-P
Change-over ...................................................................................................... TG-A1/PT1000
Cable ............................................................................................ Type RJ12, different lengths
CO
2
-transmitter ............................................................................................................. CO2RT
Humidity sensor ................................................................................................................. HRT
Outdoor temperature sensor ............................................................................. TG-UH/PT1000
Cables for connection between RU and RCP
Length 3 m ............................................................................................................ RU-CBL3
Length 10 m ......................................................................................................... RU-CBL10
The accessories are available from Regin. For more information, see the product sheets and
instructions for each product, search via
www.regin.se
.
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...