90
Part V
Signals
RCPSettings.RegioALarmCategory(1) X,3 106
3
Alarm category for presence:
0 = A alarm
1 = B alarm
2 = C alarm
3 = Event
4 = Disabled
RCPSettings.RegioALarmCategory(2)
X,3
107
3
Alarm category for open window
RCPSettings.RegioALarmCategory(3)
X,3
108
0
Alarm category for condensation
RCPSettings.RegioALarmCategory(4)
X,3
109
0
Alarm category for room temp high
RCPSettings.RegioALarmCategory(5) X,3 110
0
Alarm category for room temp low
RCPSettings.RegioALarmCategory(6)
X,3
111
0
Alarm category for room temp deviation
RCPSettings.RegioALarmCategory(7) X,3 112
2
Alarm category for room controller in
manual mode
RCPSettings.RegioALarmCategory(8) X,3 113
0
Alarm category for sensor alarm
RCPSettings.RegioLightFunction
X,3
114
0
Select lighting control function:
0 = Manual control
1 = Time control
2 = Presence control
3 = Time or presence control
RCPSettings.RegioLightSelect
X,3
115
2
Manual/Auto control of the lighting:
0 = Off
1 = Manual On
2 = Auto
RCPSettings.RegioJalusiRunTime
I,3
116
240 sec
Run time for controlling the blinds
in/out (sec)
RCPSettings.RegioCond_0V
R,4
117
0 %
Condensation at 0 volt input
RCPSettings.RegioCond_10V
R,4
118
100 %
Condensation at 10 volt input
RCPSettings.RegioCO2_0V R,4
119
0ppm
CO
2
at 0 V input signal
RCPSettings.RegioCO2_10V R,4
120
1000ppm
CO
2
at 10 V input signal
RCPSettings.RegioRH_0V
R,4
121
0 RH
RH at 0 V input signal
RCPSettings.RegioRH_10V
R,4
122
100 RH
RH at 10 V input signal
RCPSettings.RegioCondFilterFactor R,4
123 0.2
Filter factor for condensation on analog
input:
0 = No filter
1 = Max filter
RCPSettings.RegioCO2FilterFactor
R,4
124
0.2
Filter factor for CO
2
on analog input:
0 = No filter
1 = Max filter
RCPSettings.RegioRHFilterFactor
R,4
125
0.2
Filter factor for RH on analogue input:
0 = No filter
1 = Max filter
RCPSettings.RegioAlarmHyst R,4
126
0.2
°C
Alarm hysteresis
RCPSettings.RegioRoomTempHigh R,4
127 40°C High
room
temp
RCPSettings.RegioRoomTempLow
R,4
128
15°C
Low room temp
RCPSettings.RegioMaxDevRoom
R,4
129
20°C
Max allowed difference between
setpoint and room temp before alarm
RCPSettings.RegioCondensationLimit
R,4
130
80%
High limit for condensation alarm
RCPSettings.RegioCondensationHyst
R,4
131
2%
Condensation alarm hysteresis
RCPSettings.RegioCO2PresenceLimit R,4
132
800
Activate presence if CO
2
is higher
RCPSettings.RegioCO2PresenceHyst R,4 133 160
Diff for deactivate presence on CO
2
RCPSettings.RegioDigOutSelect(0) X,3
134 -
Not
used
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...