Regio Manual Maxi
Chapter 20
Signals
83
RCPInternal.RegioNotUsedL L,2
30
Not
used
RCPInternal.RegioNotUsedL L,2
31
Not
used
RCPInternal.RegioNotUsedL L,2
32
Not
used
RCPInternal.RegioNotUsedL L,2
33
Not
used
RCPInternal.RegioNotUsedL L,2
34
Not
used
RCPInternal.RegioNotUsedL L,2
35
Not
used
RCPInternal.RegioNotUsedL L,2
36
Not
used
RCPActual.RegioCIn
L,2
37
Value of condensation input.
RCPActual.RegioLighting
L,2
38
Indicate lightning is on
RCPActual.RegioSumAlarm L,2
39
Indicate sum alarm
RCPActual.RegioJalusi
L,2
40
Indicate jalusi is out
RCPActual.RegioCO2Presence
L,2
41
Indicate presence from CO
2
sensor
RCPActual.RegioTGOccupied L,2
42
Is
set if timechannel Occupied is active
RCPActual.RegioTGUnOccupied
L,2
43
Is set if timechannel Unoccupied is
active
RCPActual.RegioTGLighting
L,2
44
Is set if timechannel lightning is active
RCPActual.RegioAlaPt(1) L,2 45
Indicate
presence
RCPActual.RegioAlaPt(2) L,2
46 Indicate
Open
window
RCPActual.RegioAlaPt(3) L,2
47
Condensation
alarm
RCPActual.RegioAlaPt(4)
L,2
48
Room temp high
RCPActual.RegioAlaPt(5)
L,2
49
Room temp low
RCPActual.RegioAlaPt(6)
L,2
50
Room temp deviation
RCPActual.RegioAlaPt(7)
L,2
51
Room controller in manual mode
RCPActual.RegioAlaPt(8) L,2
52
Sensor
alarm
Coil Status Register
Signal name
Type
Modbus
address
Default
value
Description
RCPSettings.RegioBypass
L,1
1
0
Force the unit in Bypass mode. Is
automaticly returned after Bypass time
(default=120 min)
RCPSettings.RegioShutDown
L,1
2
0
Force the unit in ShutDown state
RCPInternal.RegioNotUsedL
L,1
3 0 Not
used
RCPSettings.RegioDiNC(0)
L,1
4 0 Not
used
RCPSettings.RegioDi1NC
L,1
5
0
Normaly open (NO) or normaly closed
(NC) on digital input 1. 0=NO, 1=NC.
RCPSettings.RegioDi2NC
L,1
6
1
Normaly open (NO) or normaly closed
(NC) on digital input 2. 0=NO, 1=NC.
RCPSettings.RegioDi3NC
L,1
7
0
Normaly open (NO) or normaly closed
(NC) on digital input 3. 0=NO, 1=NC.
RCPInternal.RegioNotUsedL
L,1
8 0 Not
used
RCPInternal.RegioNotUsedL
L,1
9 0 Not
used
RCPInternal.RegioNotUsedL L,1
10
0
Not
used
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...