88
Part V
Signals
RCPSettings.RegioDo4
X,3
38
4
Connected signal on DO4
RCPSettings.RegioDo5
X,3
39
0
Connected signal on DO5
RCPSettings.RegioDo6
X,3
40
5
Connected signal on DO6
RCPSettings.RegioDo7
X,3
41
6
Connected signal on DO7
RCPInternal.RegioNotUsedX X,3
42
-
Not
used
RCPInternal.RegioNotUsedX X,3
43
-
Not
used
RCPSettings.RegioModbusSlaveAddr X,3 44
Modbus
slave
address
RCPSettings.RegioModbusParity
X,3
45
2
Modbus parity bit:
0 = No parity bit
1 = Odd parity bit
2 = Even parity bit
RCPInternal.RegioNotUsedX X,3
46
-
Not
used
RCPInternal.RegioNotUsedX X,3
47
-
Not
used
RCPSettings.RegioDispBacklightLO
X,3
48
20
Display lighting low (0…255)
RCPSettings.RegioDispBacklightHi
X,3
49
100
Display lighting high (0…255)
RCPSettings.RegioDispContrast X,3
50
15
Contrast
(0…15)
RCPSettings.RegioDisplayViewMode
X,3
51
0
Select viewmode for the display:
0 = Room temp
1 = Heat setpoint
2 = Cool setpoint
3 = Average cool/heat setpoint
4 = Only setpoint offset
RCPInternal.RegioNotUsedX X,3
52
-
Not
used
RCPInternal.RegioNotUsedX X,3
53
-
Not
used
RCPInternal.RegioNotUsedX X,3
54
-
Not
used
RCPInternal.RegioNotUsedX X,3
55
-
Not
used
RCPSettings.RegioBypassTime
I,3
56
120 min
Time in Bypass mode (min)
RCPSettings.RegioPresenceOffTime
I,3
57
10 min
Off delay for changing to no presence
(min)
RCPSettings.RegioPresenceOnTime
I,3
58
0 min
On delay for changing to presence (min)
RCPSettings.RegioCVHeatPeriodTime I,3 59
60
sec
Period time if pulse prop. control valves
heating (sec)
RCPSettings.RegioCVCoolPeriodTime
I,3
60
60 sec
Period time if pulse prop. control valves
cooling (sec)
RCPSettings.RegioCVHeatRunTime
I,3
61
120 sec
Run time close to open valve heating
(sec)
RCPSettings.RegioCVCoolRunTime
I,3
62
120 sec
Run time close to open valve cooling
(sec)
RCPInternal.RegioNotUsedX X,3
63
-
Not
used
RCPInternal.RegioNotUsedX X,3
64
-
Not
used
RCPInternal.RegioNotUsedX X,3
65
-
Not
used
RCPInternal.RegioNotUsedX X,3
66
-
Not
used
RCPInternal.RegioNotUsedX X,3
67
-
Not
used
RCPSettings.RegioOccSetPHeat
R,3
68
22 °C
Basic heating setpoint
RCPSettings.RegioOccSetPCool
R,3
69
24 °C
Basic cooling setpoint
RCPSettings.RegioStandbySetPDeadBand R,3
70
3 °C
Deadband in Standby mode
RCPSettings.RegioUnOccSetPHeat
R,3
71
15 °C
Heating setpoint in Unoccupied mode
RCPSettings.RegioUnOccSetPCool
R,3
72
30 °C
Cooling setpoint in Unoccupied mode
RCPSettings.RegioFrostSetP
R,3
73
8 °C
Frost protection setpoint
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...