Regio Manual Maxi
Chapter 9
Operating modes
55
Maxi can be controlled using local time control. This means that there are two time channels,
one time channel Occupied for changing between Stand-by and Occupied, and one time
channel Unoccupied for changing between Stand-by and Shutdown. If both time channels are
active at the same time, the time channel for Occupied will take precedence.
The Occupancy button
Pressing the Occupancy button overrides the local time control. I. e. if the controller is in
Occupied mode and you press the Occupancy button, Bypass will be activated for 2 hours.
The controller will then return to Occupied. If you press the Occupancy button again when
the controller is in Bypass mode, Stand-by will be activated even if time channel Occupied is
on.
If you press the Occupancy button when the controller is in Bypass and time channel
Unoccupied is on, the controller will change to Shutdown instead of Stand-by.
When the Occupancy button is held depressed for more than 5 seconds, the controller
changes operating mode to Shutdown, regardless of the time control.
Central control
Central control of the operating mode is also possible. By changing the variable
RegioRemoteState
, you can control the operating mode centrally according to the following
table (there is a variable list for central control in Part V of this manual):
RegioRemoteState
Description
0
Central operating mode Off
1
Central operating mode Unoccupied
2
Central operating mode Stand-by
3
Central operating mode Occupied
4 (Not
used)
5 (FS)
No central control
Table 9. The variable RegioRemoteState
The occupancy button
When using central control (i. e. RegioRemoteState <> 5) and you press the Occupancy
button, the controller will change to Bypass and stay in this mode for as long time as you
have configured. If you press the Occupancy button again when the controller is in Bypass,
the controller will change to Stand-by, regardless of what has been set in the central control
(RegioRemoteState).
When the controller is in Bypass and the Bypass time has run out, the controller will change
to the operating mode given by
RegioRemoteState
. If
RegioRemoteState
equals 5 it will
change to the preset operating mode.
If the controller is in Stand-by and the central control is changed, the controller will change
to this new operating mode.
Occupancy detector
When central control is used and the occupancy detector is activated, the controller will go to
Bypass for a configurable time, and thereafter return to the central operating mode.
Central command
Via central commands from a comprehensive system, for example EXO4, you can handle the
controller in the same way as you handle it locally via the Occupancy button, i. e. you can
change its operating mode to Off/Unoccupied (Shutdown) or Bypass.
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...