Regio Manual Maxi
Chapter 6
Installation
35
82
DI2
Window contact, potential-free, NO. Open contact corresponds
to closed window (FS).
Wiring:
Potential-free contact is connected between terminals 82 and 80,
+C.
Alternatives:
- Condensation detector, potential-free, NO. Open contact
corresponds to no condensation.
- Occupancy detector, potential-free, NO. Open contact
corresponds to absence.
- Change-over sensor, potential-free, NO. Open contact
corresponds to heating demand.
See Regio tool
©
for
configuration of
NO/NC. The
factory setting is
normally open
(NO) contacts, but
the contacts can be
configured to NC.
83
+C
24 V DC out common for DI3.
84
DI3
Change-over, potential-free, NO. Open contact corresponds to
heating demand (FS).
For switching between heating and cooling on a two-pipe
system.
Wiring:
Potential-free contact is connected between terminals 84 and 83,
+C.
Alternatives:
- Window contact, potential-free, NO. Open contact corresponds
to closed window.
- Condensation detector, potential-free, NO. Open contact
corresponds to no condensation.
- Occupancy detector, potential-free, NO. Open contact
corresponds to absence.
See Regio tool
©
for
configuration of
NO/NC. The
factory setting is
normally open
(NO) contacts, but
the contacts can be
configured to NC.
90-92
No
function
Table 6. I/O connection terminals for RCP100F, RCP100FT and RCP100FL
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...