Regio Manual Maxi
Chapter 17
Display handling
69
6
Frost protection setpoint
8°C
7
P-band for room controller
10°C
8
I-time (s) for room controller
300 s
9
With a lower temperature on the analogue Change-over input,
the cooling function is selected
18
10
With a higher temperature on the analogue Change-over input,
the heating function is selected
22
11
Control states: 0=Heat, 1=Heat/Heat, 2=Heat or cooling via
Change-over, 3=Heat/Cooling , 4=Heat/Cooling with VAV-
control and forced supply air, 5=Heat/Cooling with VAV
control, 6=Cooling, 7=Cooling/Cooling
3
12
Time in Bypass mode
120 min
13 Disconnect
timer
with
occupancy/unoccupancy 10
min
14
Switch on delay for occupancy
0 min
15
State connected sensor on AI1:
0= None, 1=Room sensor, 2=Change-over, 3=Condensation
detector, 4=Outdoor sensor, 5=CO
2
, 6=Humidity sensor
1
16
State connected sensor on AI2:
The same options as for AI1 (see above).
2
17
State connected sensor on DI1:
0=None, 1=Window contact, 2= Condensation detector,
3=Presence, 4=Change-over
3
18
State connected sensor on DI2:
The same options as for DI1.
1
19
State connected sensor on DI3:
The same options as for DI1.
2
20
State function of signal on AO1:
0=None, 1=Heating actuator, 2=Cooling actuator
1
21
State function of signal on AO2:
0=None, 1=Heating actuator, 2=Cooling actuator
2
22
State function of signal on DO1:
0=Ingen, 1=Fan speed 1, 2=Fan speed 2, 3=Fan speed 3,
4=Forced ventilation, 5=Thermal actuator heating, 6=Thermal
actuator cooling, 7=Heating actuator increase, 8=Heating
actuator decrease, 9=Cooling actuator increase, 10=Cooling
actuator decrease, 11=Lighting, 12=Control of blinds open,
13=Control of blinds close
RCP100=4
RCP200=4
RCP100-F=1
RCP200-F=1
23
State function of signal on DO2:
The same options as for DO1.
RCP100=0
RCP200=0
RCP100-F=2
RCP200-F=2
24
State function of signal on DO3:
The same options as for DO1.
RCP100=5
RCP200=0
RCP100-F=3
RCP200-F=3
25
State function of signal on DO4:
The same options as for DO1.
RCP100=6
RCP200=0
RCP100-F=4
RCP200-F=4
26
State function of signal on DO5:
The same options as for DO1.
RCP100=0
RCP200=0
RCP100-F=0
RCP200-F=0
27
State function of signal on DO6:
The same options as for DO1.
RCP100=0
RCP200=0
RCP100-F=5
RCP200-F=0
28
State function of signal on DO7:
The same options as for DO1.
RCP100=0
RCP200=0
RCP100-F=6
RCP200-F=0
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...