Input Status Register
Signal name
Type
Modbus
address
Default
value
Description
RCPActual.RegioDigIn(0) L,2
1
Not
used
RCPActual.RegioDigIn1
L,2
2
Value of digital input 1.
RCPActual.RegioDigIn2
L,2
3
Value of digital input 2.
RCPActual.RegioDigIn3
L,2
4
Value of digital input 3.
RCPActual.RegioDigOut(0) L,2
5
Not
used
RCPActual.RegioDigOut1
L,2
6
Value of digital output 1.
RCPActual.RegioDigOut2
L,2
7
Value of digital output 2.
RCPActual.RegioDigOut3
L,2
8
Value of digital output 3.
RCPActual.RegioDigOut4
L,2
9
Value of digital output 4.
RCPActual.RegioDigOut5
L,2
10
Value of digital output 5.
RCPActual.RegioDigOut6
L,2
11
Value of digital output 6.
RCPActual.RegioDigOut7
L,2
12
Value of digital output 7.
RCPActual.RegioDIOpenWindow L,2
13 Indicate
open
window
RCPActual.RegioDICondensationAlarm
L,2
14
Indicate condensation alarm from digital
input
RCPActual.RegioDIPresences L,2
15
Indicate presence from digital input
RCPActual.RegioDIChangeOver L,2
16 Indicate change over from digital input
RCPActual.RegioFanSpeed1
L,2
17
Indicate fan speed 1
RCPActual.RegioFanSpeed2
L,2
18
Indicate fan speed 2
RCPActual.RegioFanSpeed3
L,2
19
Indicate fan speed 3
RCPActual.RegioForcedventilation
L,2
20
Indicate forced ventilation
RCPActual.RegioCVHeatPulsProp L,2
21
Indicate puls prop heating
RCPActual.RegioCVCoolPulsProp
L,2
22
Indicate puls prop cooling
RCPActual.RegioCVHeatInc L,2
23
Indicate increase heating
RCPActual.RegioCVHeatDec
L,2
24
Indicate decrease heating
RCPActual.RegioCVCoolInc L,2
25
Indicate increase cooling
RCPActual.RegioCVCoolDec L,2
26
Indicate decrease cooling
RCPActual.RegioAIChangeOverState L,2 27
Indicate change over state from analog
input
RCPActual.RegioChangeOverState L,2
28
Indicate change over state from both
digital and analog input
RCPActual.RegioRoomTempSensorAlar
m
L,2
29
Indicate sensor alarm on room sensor
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...