Regio Manual Maxi
Chapter 5
Installation preparations
19
Setting the dipswitches in RU (only models without display)
RU-models without display have four dipswitches (SW1-4) for setting basic functions. They
are found on the back of the electronics cassette.
Figure 3. Dipswitches
SW1-2
Basic setpoint (°C)
SW1
SW2
20 OFF
OFF
22 (FS)
OFF
ON
24 ON
OFF
26 ON
ON
Table 3. Setting of basic heating setpoint with dipswitch SW1 and SW2
See also the chapter
Setpoint calculation
for setting of SW1-2.
SW3
Occupied is the preset operating mode, SW3: OFF (FS). If you want the preset operating
mode to be Stand-by, set SW3 in mode ON. For more information, see the chapter
Operating
modes.
SW4
Not used.
RU-models with display
There are no dipswitches in RU-models with display. For these models, the corresponding
settings are made in the parameter menu in the display or using Regio tool
©
, see the chapter
Display handling
.
Summary of Contents for Regio Maxi
Page 1: ...Regio Maxi Manual ...
Page 4: ...4 Part I Introduction P Pa ar rt t I I I In nt tr ro od du uc ct ti io on n ...
Page 12: ...12 Part I Introduction Design of the RU models RU RU O RU DO RU F RU FO RU DFO RU DOS ...
Page 16: ...16 Part II Installation P Pa ar rt t I II I I In ns st ta al ll la at ti io on n ...
Page 78: ...78 Part V Signals P Pa ar rt t V V S Si ig gn na al ls s ...
Page 96: ...96 Part VI Index P Pa ar rt t V VI I I In nd de ex x ...