Installation
12 — English
— 03.09.2020 - Rev. A
7.3.5
Fitting the level sensor
ATTENTION
Damage to the pressure load cell due to unprofessional installation
Incorrect installation may result in damage to the "LIS" level sensor,
malfunctioning and incorrect measurements from the pressure load cell.
•
Comply with the instructions regarding the installation of the pressure
load cell.
The "LIS" level sensor uses a pressure load cell. This pressure pick-up is to be
installed after the primary vessel has been placed at its final position, see
chapter 7.3.2 "Tank installation" on page 10 . Comply with the following
instructions:
•
Remove the transport securing device (squared timber) at the vessel base
of the primary vessel.
•
Replace this transport securing device with the pressure load cell.
–
In the case of a vessel volume of 1000 l (Ø 1000 mm) or more, use the
supplied screws to attach the pressure load cell at the vessel base of
the primary vessel.
•
Avoid shock-type loading of the pressure load cell by, for example,
subsequent alignment of the vessel.
•
Use flexible hoses to connect the primary vessel and the first secondary
vessel.
–
Use only the supplied connection sets, see chapter 7.3.2 "Tank
installation" on page 10 .
•
Perform a null balancing of the filling level when the primary vessel is
aligned and fully emptied, see chapter 10.3 "Configuring settings in the
controller" on page 18 .
Standard values for level measurements:
Primary vessel
Measuring range
200 l
0 – 4 bar
300 – 500 l
0 – 10 bar
600 – 1000 l
0 – 25 bar
1500 – 2000 l
0 – 60 bar
3000 – 5000 l
0 – 100 bar
7.4
Make-up and degassing variants
7.4.1
Function
The filling level is recorded in the primary tank by the "LIS" level sensor and
evaluated in the controller. When the water level falls below the value specified
in the controller's customer menu, the external make-up is activated.
7.4.1.1
Make-up without pump
Reflexomat RS Touch with solenoid valve and ball valve.
1
WC
Make-up pipe
2
Solenoid valve "Fillvalve" with ball
valve
LIS
Level sensor
3
Reflex Fillset
EC
Expansion pipe
ST Dirt trap
Preferably, you should use the Reflex Fillset with integrated system separator
when using drinking water for make-up. If you don't use a Reflex Fillset, you
must use an "ST" dirt trap with a mesh size ≥
0.25 mm for the make-up.
7.4.1.2
Make-up with pump
Reflexomat RS Touch with Reflex Fillcontrol Auto
1
ST Dirt trap
2
Fillcontrol Auto
EC Expansion pipe
WC Make-up pipe
LI
S
Level sensor
Water make-up with Fillcontrol Auto is suitable for make-up at high system
pressures of up to 8.5 bar. The "ST" dirt trap is part of the deliverables.
7.4.1.3
Make-up with softening and degassing
Reflexomat RS Touch and Reflex Servitec.
1
ST
Dirt trap
2
Reflex Servitec
WC Make-up pipe
3
Reflex Fillsoft
LIS Level sensor
4
Reflex Fillset Impulse
EC Expansion pipe
The Reflex Servitec degassing and make-up station degasses the water from the
facility system and the make-up water. The automatic water make-up for the
facility system is controlled by the pressurisation system. Reflex Fillsoft
additionally softens the make-up water.
•
Reflex Servitec degassing and make-up station, see chapter 4.6 "Optional
equipment and accessories" on page 5 .
•
Reflex Fillsoft softening systems and Reflex Fillset Impulse, see chapter 4.6
"Optional equipment and accessories" on page 5 .
Note!
When using Reflex Fillsoft softening systems, always install the Reflex
Fillset Impulse.
–
The controller evaluates the make-up quantities and signals a
required replacement of the softening cartridges.