Installation
— 03.09.2020 - Rev. A
English — 13
7.5
Electrical connection
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the device.
•
Ensure that the system is secured and cannot be reactivated by other
persons.
•
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical
engineering regulations.
For the electrical connection, you must differentiate between a connection
component and an operating component.
Example: Control unit with one compressor
1
Connection component cover (hinged)
2
Operating unit cover (hinged)
•
RS-485 interfaces
•
Pressure and Level outputs
3
Touch control
4
Connection component rear
5
Cable bushings
•
Supply and fusing
•
Floating contacts
•
"CO" compressor connection
The following descriptions apply to standard systems and are limited to the
necessary user-provided connections.
1.
Disconnect the system from the power source and secure it against
unintentional reactivation.
2.
Remove the covers.
DANGER Risk of serious injury or death due to electric shock. Some
parts of the device's circuit board may still be live with 230 V even after the
device has been physically isolated from the power supply by pulling out of
the mains plug. Before you remove the covers, completely isolate the
device controller from the power supply. Verify that the main circuit board
is voltage-free.
3.
Insert a suitable screwed cable gland for the cable bushing at the rear of
the connection component. M16 or M20, for example.
4.
Thread all cables to be connected through the cable glands.
5.
Connect all cables as shown in the terminal diagrams.
–
Connection unit, see chapter 7.5.1 "Terminal plan, connection
component" on page 13 .
–
Operating unit, see chapter 7.5.2 "Terminal plan, operating unit" on
page 14 .
–
For installer supplied fusing, comply with the connected loads of the
device , see chapter 6 "Technical data" on page 8 .
7.5.1
Terminal plan, connection component
1
Pressure
3
Fuses
2
Level
Terminal
number
Signal
Function
Wiring
Supply
X0/1
L
230 V supply
Reflexomat RS 90
User supplied
X0/2
N
X0/3
PE
X0/1
L1
400 V supply
Reflexomat RS 150 ... 580
User supplied
X0/2
L2
X0/3
L3
X0/4
N
X0/5
PE
Circuit board
4
Y1
WV make-up valve
User,
optional
5
N
6
PE
7
Y2
PV 1 solenoid valve
User supplied
8
N
9
PE
13
Dry-run protection message
(floating)
User,
optional
14
23
NC
Group message (floating)
User,
optional
24
COM
25
NO
35
+18 V (blue)
Analogue input, LIS level
measuring
at the primary vessel
User supplied
36
GND
37
AE (brown)
38
PE (shield)
39
+18 V (blue)
PIS pressure sensor analogue
input at the primary vessel
User,
optional
40
GND
41
AE (brown)
42
PE (shield)
43
+24 V
Digital inputs
User,
optional
44
E1
E1: Contact water meter
Factory-
provided
1
PE
Voltage supply
Not assigned
2
N
3
L