background image

 

Installation 

 

 

 

 — 03.09.2020 - Rev. A 

 

English  — 11 

 

 

 

The following typical example describes the installation of the control unit 
upstream of the primary vessel and the connection of two secondary vessels. 
Proceed accordingly for other installation variants. 

 

 

 

 

 

Expansion pipe 

 

SV  Safety valve 

Compressed air line 

 

PV  Solenoid valve 

Data line 

 

PIS  Pressure sensor 

RF  Secondary vessel 

 

AC  Compressed air line 

RG  Primary vessel 

 

EC  Expansion pipe 

 

 

7.3.3.1

 

Water-side connection 

 

To ensure the proper function of the "LIS" level sensor, you must use the 
supplied hose to flexibly connect the primary vessel to the system. 
The "EC" expansion line provides secure locking and emptying for primary vessel 
and the optional secondary vessels. If more than one vessel is used, a collective 
line to the system is installed. 
Use points with temperatures between 0 °C and 70 °C to connect to the system. 
This is the return of the generator in heating systems and the flow in 
refrigeration systems.  
At temperatures below or above 0 °C – 70 °C, you must install in-line vessels 
between the system and the Reflexomat. 

 

 

Note! 
For details regarding the switching of Reflexomats or in-line vessels and 
the dimensions of the expansion lines, please see the planning 
documents. More information is also provided in the Reflex Planning 
Guide. 

 

 

7.3.3.2

 

Control unit connection 

 

• 

The "PV" solenoid valve, the "PIS" pressure transducer and the 

corresponding cables are factory-installed on the primary vessel.  

–  

Run the cable through the assembly pipe on the rear of the primary 
vessel to the control unit.  

 

• 

Subsequently install the level sensor at the primary vessel, see 
chapter 7.3.5 "Fitting the level sensor" on page 12 .  
–  

Attach the cable to the "LIS" pressure pick-up of the level sensor and 
run the cable to the control unit.  

• 

The flexible compressed air hose is connected with the control unit. Run 
the compressed air hose through the assembly pipe as well.  
–  

Control unit with one compressor:  
• 

Connect the compressed air line directly to the "AC" 
compressed air connection of the primary vessel.  

–  

Control unit with two compressors or additional secondary vessel:  
• 

First install the supplied distributor at the "AC" compressed air 
connection of the primary vessel. 

• 

Connect the compressed air lines of the compressors via the 
distributor. 

• 

Use the supplied connection sets to connect the secondary 
vessels.  

 

 

7.3.4

 

Connection to an external compressed air line 

 

An external pressure supply can optionally be connected to the Reflexomat. 
When doing so it must be ensured that a pressure reducer is fitted in the external 
pressure line. The minimum pressure to be set depends on the relevant pressure 
rating of the vessel. 

 

 

Pressure reducer, site attachment 

  PIS 

Pressure sensor 

Dirt trap, site attachment 

  SV 

Safety valve 

Pressure gauge, site attachment 

  PV 

Overflow solenoid valve 

Solenoid valve, supplied by Reflex 

  LIS 

Level sensor 

 

Instead of the compressor, a solenoid valve is actuated in the external 
compressed air line, which releases the compressed air for the vessel. The 
solenoid valve is activated by the controller. The electrical connection of the 
solenoid valve is made via the terminal for the compressor in the respective 
controller. 
Properties of the external compressed air: 
• 

Quality 
–  

Fluid group 2 according to the Pressure Equipment Directive 2014 / 
68 EU. 

–  

DIN ISO 8573-1 Class 1. 

• 

Oil-free 
–  

ATTENTION Diaphragm damage caused by oil-containing 
compressed air. Keep the compressed air free of oil. 

• 

Compressed air 
–  

ATTENTION Damage to the vessel. The compressed air must be 
reduced to the respective vessel pressure rating. 

 

 

Note! 
See chapter "Terminal plan" for the solenoid valve electrical connection. 

 

Cooke Industries - Phone: +64 9 579 2185    Email: [email protected]    Web: www.cookeindustries.co.nz

Summary of Contents for Reflexomat RS 150/1 T

Page 1: ...400 1 T RS 580 1 T RS 90 2 T RS 150 2 T RS 300 2 T RS 400 2 T RS 580 2 T external air T GB Operating manual Original operating manual Reflexomat Touch Cooke Industries Phone 64 9 579 2185 Email sales...

Page 2: ...ng the level sensor 12 7 4 Make up and degassing variants 12 7 4 1 Function 12 7 5 Electrical connection 13 7 5 1 Terminal plan connection component 13 7 5 2 Terminal plan operating unit 14 7 5 3 RS 4...

Page 3: ...re irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe the safety information can result in minor reversible injurie...

Page 4: ...rs as stand alone console Note The connection of RF secondary vessels to the RG primary vessel is optionally possible 4 2 Overview Reflexomat with touch control and one compressor 1 Main switch 5 RF s...

Page 5: ...and sends this value to the controller of the pressure maintaining station This controls an external make up Water is directly added into the system in a controlled manner by monitoring the make up t...

Page 6: ...e already contained in the Control Touch controller Interfaces to the controller RS 485 19 2 kbit s Floating connection with plug or screw terminals RSI specific protocol 5 2 Settings GEFAHR Danger to...

Page 7: ...d adjusted to local conditions Responses by the inputs 1 6 of the I O module are recorded and displayed in the device controller s fault memory Note Default settings apply to software version V1 10 an...

Page 8: ...connect the I O module from the power supply Pull the power plug from the bus module 2 Open the terminal space cover 3 Remove the housing cover 4 Replace the defective fuse 5 Re attach the housing cov...

Page 9: ...s to the skin Wear protective gloves Please place appropriate warning signs in the vicinity of the device CAUTION Risk of injury due to falls or bumps Bruising from falls or bumps on system components...

Page 10: ...s or equipment Comply with the following notes regarding the installation of the primary vessel and the secondary vessels All flange openings at the vessels are viewing and maintenance openings Place...

Page 11: ...he flexible compressed air hose is connected with the control unit Run the compressed air hose through the assembly pipe as well Control unit with one compressor Connect the compressed air line direct...

Page 12: ...er When the water level falls below the value specified in the controller s customer menu the external make up is activated 7 4 1 1 Make up without pump Reflexomat RS Touch with solenoid valve and bal...

Page 13: ...covers completely isolate the device controller from the power supply Verify that the main circuit board is voltage free 3 Insert a suitable screwed cable gland for the cable bushing at the rear of t...

Page 14: ...ve 12 R D 13 T D 14 GND IO2 15 10 V 10 V supply Factory 16 17 FE 18 Y2PE shielding Analogue outputs Pressure and Level Standard 4 20 mA User supplied 19 Pressure 20 GNDA 21 Level 22 GNDA 7 5 3 RS 485...

Page 15: ...ar for safety temperatures 110 C Addition of 0 2 bar recommended no addition in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus ex...

Page 16: ...te After successful conclusion of the start routine you are in Stop mode Do not yet switch to Automatic mode 8 4 Venting the vessels CAUTION Risk of burns on hot surfaces Excessive surface temperature...

Page 17: ...on is highlighted green The function is switched off Press the desired button The button is highlighted blue The function is switched on The change in the filling level and the vessel pressure are ind...

Page 18: ...flexomat switching points on page 15 Make up 021 Make up ON at 022 Make up OFF at 023 Maximum make up time min 024 Maximum make up cycles 2 h 027 With contact water meter Yes No If Yes continue with 0...

Page 19: ...P0 0 4 bar Differential pressured added to the P0 minimum operating pressure Overflow line OPEN P0 0 5 bar Differential pressured added to the P0 minimum operating pressure Maximum pressure P0 3 bar...

Page 20: ...tioning Dirt trap clogged Check set value in the Customer or Service menu Check functioning of the pressure relief pipe Clean the dirt trap OK 11 Make up volume Only if With water meter is activated i...

Page 21: ...e secondary vessels if applicable see chapter 11 3 1 Cleaning the tanks on page 22 x x x Annually 11 2 Checking switching points Prerequisite for checking the switching points are the following correc...

Page 22: ...er for the residual pressure to escape from the pipeline segment 4 Pull the mesh from the dirt trap insert and rinse it with clear water Use a soft brush for cleaning 5 Re insert the mesh into the dir...

Page 23: ...m the power supply 3 Disconnect and remove all cables from the terminals of the device controller DANGER Risk of serious injury or death due to electric shock Some parts of the device s circuit board...

Page 24: ...en installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match the local conditions sagdr Typ Type P0 PSV Fabr Nr Serial No Coo...

Page 25: ...ex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www c...

Reviews: