Controller
18 — English
— 03.09.2020 - Rev. A
10.2
Calibrating the touch screen
You can calibrate the touch screen when touching the desired buttons does not
work satisfactorily.
1.
Switch the device off at the main switch.
2.
Touch and hold the touch field with your finger.
3.
Switch on the main switch while touching the touch field.
–
When starting the program, the controller automatically switches to
the "Update/Diagnostics" function.
4.
Touch the "Touch calibration" button.
5.
Touch the displayed crosses on the touch screen after each other.
6.
Switch the device off and on again at the main switch.
The touch screen is fully calibrated.
10.3
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
10.3.1.1
Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the
course of initial commissioning, the factory settings must be adjusted for the
system-specific conditions.
Note!
For a description of the operation, see chapter 10.1 "Operator panel" on
page 17 .
A three-digit PM code is assigned to the setting options
PM
Code
Description
001
Select the language
002
Set the time
003
Set the date
Execute null balancing
–
The primary vessel must be empty!
–
The system checks whether the signal from the level sensor
matches the selected primary vessel.
005
Set the minimum operating pressure P
0
, see chapter 8.2
"Reflexomat switching points" on page 15 .
Make-up >
021
•
Make-up ON at …%
022
•
Make-up OFF at …%
023
•
Maximum make-up time …min
024
•
Maximum make-up cycles … /2 h
027
•
With contact water meter "Yes/'No"
–
If "Yes", continue with 028
028
•
Reset make-up volume "Yes/No".
029
•
Maximum make-up volume ... l
PM
Code
Description
030
•
With softening "Yes/'No"
–
If "Yes", continue with 031
031
•
Shut off make-up "Yes/No" (if water capacity is exhausted)
033
•
Hardness reduction … °dH = GHactual – GHtarget
032
•
Soft water capacity
–
Fillsoft I: Soft water capacity = 6000 l / hardness
reduction
–
Fillsoft II: Soft water capacity = 12000 l / hardness
reduction
034
•
replacement interval… months (for softening cartridges
according to manufacturer).
007
Maintenance interval… months
008
Floating contact
•
Message selection >
–
Message selection: only messages marked with "√" are
output.
–
All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009
•
Brightness … %
010
•
Screen saver brightness … %
011
•
Screen saver delay …min
Information >
•
Vessel: Vessel information
•
Software version
10.3.1.2
Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1.
Press "Settings".
–
The controller switches to the setting area.
2.
Press "Customer >".
–
The controller opens the Customer menu.
3.
Press the required area.
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.