Diagram 5
E
F
G
Installed in an
insulated wall
In conduit
trunking
Clipped direct
or buried in a
non-insulated
wall
6 mm
32A
10 mm
43A
16 mm
57A
I
I
2
2
2
6 mm
38A
10 mm
52A
16 mm
69A
I
I
2
2
2
6 mm
46A
10 mm
63A
16 mm
85A
I
I
2
2
2
Twin and earth PVC insulated cable
Current carrying capacity
8.5kW
9.5kW
10.8kW
I
I
40A
40/45A
45A
I
I
45A
45A
45A
I
I
Unit
Rating
MCB
Cartridge
Fuse
CIRCUIT PROTECTION
Note:
Cable selection is dependent on derating
factors
8
entry points then the following backplate
component will need to be discarded allowing
for the conduit to fit into the backplate. See
Diagram 5 - Option
‘E’
or
‘F’
.
If the installation requires the use of 10mm²
cable up through the Bottom Entry option, then
you will need to remove the appropriate
backplate section
‘G’
shown in Diagram 5.
(
*
See limitations on 16mm² on Page 9).
Rear cable entry is permissible within the
service channel area
“H” shown in diagram 5.
The position will be dependent on the chosen
water entry.
The cable connected to the appliance must be
fixed wiring, and should be stripped back as
shown in Diagram 7
Connect the cable to the terminal block.
Ensure that all the retaining screws are
VERY
tight and that no cable insulation is trapped
under the screws.
Warning!
Failure To Comply With
These Instructions Could Result In
A Failure Of The Terminal Block.
Warning!
This Appliance Must Be
Earthed
Replace the
trimplate section complete with seal.
inlet cover and side access
Diagram 6
H
*
*
*