64
Figure 11-9 - PVC/CPVC air intake/
vent connection
A = MOMENTIVE - RTV 106
high temperature silicone (or
equivalent) (Field provided)
B = Flue exhaust adapter for
PVC/CPVC pipe
F = mechanically secure clamp
G = PVC/CPVC exhaust pipe
(Field provided)
H = Combustion analization
probe (Field installed)
L = cap (Field provided)
N = PVC/CPVC air inlet pipe
(Field provided)
P = Air intake adapter for PVC/
CPVC pipe
A
B
F
P
F
H
G
A
L
N
020010.01.010
Combustion
air intake
Flue
exhaust
Figure 11-10 - PVC/CPVC
air intake/Vent connection
correctly in place
Extend the
flue exhaust
pipe to
outside
building
020010.01.016
Extend the
air intake
pipe to
outside
building
11 - INSTALLATION - CATEGORY IV: Vent and combustion air
11.6.2 - PVC/CPVC air
intake connection
Combustion Air Intake
connection (see Figure 11-9
Item “P”).
This connection is used
to provide combustion air directly to the
appliance from outdoors. Combustion
air piping must be supported per
guidelines listed in the National
Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
To connect a PVC/CPVC pipe to the
air intake connection proceed as follow
while referring to Figure 11-9:
1.- Prepare the connection between
adapter “P” and pipe “N” like
described on Section 11.6.1;
2.- Insert the air inlet PVC/CPVC pipe,
for 3” into the adapter “P”;
3.- Tighten the clamp “F” to
mechanically secure the adapter “P”
to the pipe.
11.6.3 - PVC/CPVC vent
connection
Vent connection (see Figure
11-9 Item “C”)
.
This connection
is used to provide a passageway for
conveying combustion gas to the
outside.
Vent piping must be supported per the
National Building Code, Section 305,
Table 305.4 or as local codes dictate.
To connect a PVC/CPVC pipe to the
vent connection proceed as follow
while referring to Figure 11-9:
1.- Prepare the connection between
adapter “B” and pipe “G” like
described on Section 11.6.1;
2.- Insert the flue exhaust PVC/CPVC
pipe, for 3” into the adapter “B”;
3.- Tighten the clamp “F” to
mechanically secure the adapter “B”
to the pipe.
WARNING!!!
Do not cover
with thermal insulation PVC/
CPVC exhaust pipe nor install
into an enclosure, closet,
alcove or any other obstruction
thereby preventing the cooling
of the exhaust pipe. Failure to
follow this warning could result
in excessive levels of carbon
monoxide or a fire, which can
result in severe personal injury
or death!
020010.01.039
CAUTION!!!
Apply a liberal
even coat of MOMENTIVE -
RTV 106 high temperature
silicone (or equivalent) to the
internal side of the appliance
adapter (item “B” and “P”
fig.11-9)