32
Combustion and ventilation air
requirements for appliances drawing
air from the equipment room.
Provisions for combustion and
ventilation air must be in accordance
with air for combustion and ventilation,
of the latest edition of the National Fuel
Gas Code, ANSI Z223.1, in Canada,
the latest edition of CGA Standard
B149 Installation Code for Gas
Burning Appliances end Equipment,
or applicable provisions of the local
building codes.
The equipment room MUST be
provided with properly sized openings
to assure adequate combustion air and
proper ventilation.
1.- If air is taken directly from outside
the building with no duct, provide two
permanent openings to the equipment
room (see Fig. 5-1);
(a) Combustion air opening, with a
minimum free area of one square
inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be
located within 12” (30 cm) of the
bottom of the enclosure;
(b) Ventilation air opening, with a
minimum free area of one square
inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be
located within 12” (30 cm) of the top
of the enclosure.
2.- If combustion and ventilation air is
taken from the outdoors using a duct to
deliver the air to the equipment room,
each of the two openings should be
sized based on a minimum free area
of one square inch per 2000 Btu/hr (11
cm
2
per kW) of input (see Fig. 5-2);
Figure 5-1 - Combustion Air direct from outside
Figure 5-2 - Combustion Air through Ducts
5 - INSTALLATION - Location
EQUIPMENT
ROOM
AIR OPENING
AIR OPENING
EQUIPMENT
ROOM
AIR OPENING
AIR OPENING
Summary of Contents for Infinite Energy2 IW1000
Page 3: ...3 SAFETY INSTRUCTIONS...
Page 5: ...5 SAFETY INSTRUCTIONS...
Page 122: ...122 16 MAINTENANCE...
Page 126: ...126 18 SPARE PARTS Spare parts...
Page 154: ...154 21 SEQUENCE OF OPERATION...