9.2 - Connecting
the appliance to a
storage tank
If the
appliance is connected to a
storage tank:
1.- The water connection must be
made per Figure 7-5;
2.- The storage tank pump (Local
pump) must be connected to
terminals “113” and “114” (See
Figure 9-3) (a field supplied pump
relay must be installed if the pump
current draw is greater than 3
amps);
3.- Remove header sensor present on
terminals “8” and “9” of Figure 9-3;
9 - INSTALLATION - Electrical connections
Figure 9-3 - Electrical customer connection for appliance connected to a storage tank
4. The storage tank temperature
sensor must be connected to
terminals “8” and “9” (See Figure
9-3). The sensor must be placed
into the storage tank in a way that
can detect the water temperature
(Follow the storage tank instruction).
Follow Section 15.5 to set the desired
storage tank temperature.
WARNING!!!
Since the
storage tank temperature sensor
wires conduct 24 Vac, they must
never run through conduits
containing 120 Vac power wires
or an electrical shock hazard will
exist.