Hardware Installation
PixelStor 5000 User Manual
Rev. 1, May 2013
5-86
If the PixelStor Storage Manager indicates a faulty module, go to the system and look for
a module with a red Status Indicator. Replace the component (drive, fan, controller,
power supply). Once the faulty module is replaced, the System Health Alert will stop
flashing.
Check for missing slot covers. Module slot covers are required to ensure proper system
airflow. Replace missing slot covers to ensure temperature stays within specified system
limits.
If the PixelStor Storage Manager indicates a temperature fault and there are no faulty
system modules, check for a sudden rise or drop in the room temperature. If the room
temperature is beyond those listed in the system specifications section of this manual
(See System Specifications) shut down the system until you are able to correct the
problem.
5.2.12
Voltage Threshold Exceeded
The system is also equipped with voltage sensors. If any voltage sensor reading indicates an
abnormal value beyond the factory threshold, the System Health Alert is triggered.
Corrective action:
Check the Web-based console for the source of the problem.
Check Status Indicator on each power supply. Replace if faulty.
Ensure that the system is connected to an appropriate power source such as the rack’s
power distribution unit (PDU) or an uninterruptible power supply (UPS).
5.2.13
Fan Failure
Fan state and fan speed are also monitored. If a fan fails or if the fan speed falls below the
factory threshold, the System Health Alert is triggered.
Corrective Action:
Check the Web-based console for the source of the problem.
If the Power Supply fan has dropped below the recommended RPM that Power Supply
should be replaced.
5.2.14
List of Health Alert Notifications:
•
The other controller is down
•
RAM ECC error is detected