73
Daily Max Time
Enter the maximum amount of accumulated on-time, in Hand or Auto modes, that the
relay can have between midnight and midnight the next day. If the time is exceeded, the
relay will deactivate, and a Daily Max Timeout alarm will be triggered. The alarm will
clear, and relay allowed to reactivate at midnight the next day.
If the relay was in Hand mode when the alarm was triggered, it will revert to whichever
HOA state it was in prior to being set to Hand.
To override the Daily Max Limit for the rest of the day, press Reset Output
Timeout.
5.3.4
Relay or Control Outputs, Bleed and Feed Control Mode
ONLY AVAILABLE IF HVAC MODES ARE ENABLED IN CONFIG MENU – GLOBAL SETTINGS
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, accumulated
on-time, alarms related to this output, current cycle on time, relay type and the current control mode setting.
Settings
Touch the Edit icon to view or change the settings related to the relay.
Feed Time Limit
Enter the maximum amount of feed time per bleed event
Bleed
Select the relay to be used for Bleed/Blowdown
Daily Max Time
Enter the maximum amount of accumulated on-time, in Hand or Auto modes, that the
relay can have between midnight and midnight the next day. If the time is exceeded, the
relay will deactivate, and a Daily Max Timeout alarm will be triggered. The alarm will
clear, and relay allowed to reactivate at midnight the next day.
If the relay was in Hand mode when the alarm was triggered, it will revert to whichever
HOA state it was in prior to being set to Hand.
To override the Daily Max Limit for the rest of the day, press Reset Output
Timeout.
5.3.5
Relay or Control Outputs, Bleed then Feed Control Mode
ONLY AVAILABLE IF HVAC MODES ARE ENABLED IN CONFIG MENU – GLOBAL SETTINGS
Output Details
The details for this type of output include the relay on/off state, HOA mode or Interlock status, accumulated
on-time, remaining feed time, the accumulated bleed time, alarms related to this output, current cycle on time,
relay type and the current control mode setting.
Settings
Touch the Edit icon to view or change the settings related to the relay.
Feed Percentage
Enter the % of bleed relay activation time to use for the feed relay activation time
Feed Time Limit
Enter the maximum amount of feed time per bleed event
Reset Timer
Use this menu to cancel the current feed cycle
Bleed
Select the relay to be used for Bleed/Blowdown