5
Low Speed Counter-Type Digital Inputs Electrical: Optically isolated and providing an electrically isolated
12VDC power with a nominal 2.3mA current when the digital input
switch is closed 0-20 Hz, 25 msec minimum width
Devices supported: Any device with isolated open drain, open collector,
transistor or reed switch
Types: Contacting Flowmeter, Flow Verify
High Speed Counter-Type Digital Inputs Electrical: Optically isolated and providing an electrically isolated
12VDC power with a nominal 2.3mA current when the digital input
switch is closed, 0-500 Hz, 1.00 msec minimum width. Minimum pulse
frequency for the rate to be displayed: 0.17 Hz
Devices supported: Any device with isolated open drain, open collector,
transistor or reed switch
Types: Paddlewheel Flowmeter, DI Counter
Outputs
Powered mechanical relays (0 to 12
depending on model code):
Pre-powered on circuit board switching line voltage. Two, three or four
relays are fused together (depending on model code) as one group, total
current for this group must not exceed 6 A (resistive), 1/8 HP (93 W)
Dry contact mechanical relays (0 to 12
depending on model code):
6 A (resistive), 1/8 HP (93 W)
Dry contact relays are not fuse protected
Pulse Outputs (0 to 12 depending on
model code):
Opto-isolated, Solid State Relay
200mA, 40 VDC Max.
VLOWMAX = 0.05V @ 18 mA
Accuracy (0-10 Hz): ± 0.5% of Pulse Rate, (10-20 Hz): ± 1.0%,
(20-40 Hz): ± 2.0%
4 - 20 mA (0 to 16 depending on model
code)
Internally powered, 15 VDC, Fully isolated
600 Ohm max resistive load
Resolution 0.0015% of span
Accuracy ± 0.5% of reading
Ethernet
10/100 802.3-2005
Auto MDIX support
Auto Negotiation
Wi-Fi
Radio Protocol: IEEE 802.11 b/g/n
Security Protocols (Ad-Hoc Mode): WPA2-Personal
Security Protocols (Infrastructure Mode): WPA/WPA2-Personal, WEP
Certifications and Compliance: FCC, IC TELEC, CE/ETSI, RoHS, Wi-Fi
Certified
NOTE on Wi-Fi:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequen-
cy energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
USB
Connector: Type A receptacle
Speed: High speed (480 Mbit)
Power: 0.5 A maximum
Battery (Real-Time Clock)
Model BR2032, 3-volt Lithium Coin Cell 20 mm diameter