Page 41
P809 Fail-safe Time
In the event of a fail-safe condition the failsafe timer determines the time
before fail-safe mode is activated.
Default = 2min
If the timer activates, the unit goes into
fail-safe
as determined by
P808
(
Display
) and
P840
(
Output
). When this happens, you will see the message
“
Failed Safe
!” on the display, along with a message explaining why (lost
comm. or comm. error, for example)
When a valid measurement is obtained then the display and output will be
restored and the timer is reset.
Auxiliary
P815 Aux Source
Determine the display on the secondary line of screen
Option
Description
0 = Units (Default)
Display the units of the main display
1 = Flow
Display flow reading
2 = Velocity
Display velocity reading
3 = Totaliser
Display resettable totaliser
mA Output Parameters
Range
P830 Output Range
This parameter determines the range of the mA output, from the following.
Option
Description
0= Off
output disabled.
1= 0 to 20 mA
output directly proportional to the
output mode
(
P831
), so if the reading is 0% the output is 0 mA. If
the reading is 100% the output is 20 mA.
2= 4 to 20 mA
(Default)
output directly proportional to the
output mode
(
P831
), so if the reading is 0% the output is 4 mA. If
the reading is 100% the output is 20 mA.
3= 20 to 0 mA
output inversely proportional to the
output mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 0 mA.
4= 20 to 4 mA
output inversely proportional to the
output mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 4 mA.
Summary of Contents for Flow Monitor
Page 1: ...Flow Monitor INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 10: ...Page 4 EU Declaration of Conformity...
Page 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Page 26: ...Page 20 This page left blank intentionally...
Page 61: ...Page 55...