Page 37
Control
P210, P220 = 2 (Control)
When a relay is being set up as a
control
relay, the
second parameter
that
will be displayed in the menu determines its
function.
P211, P221 - Relay Function,
This function is used, where it is required to
energise
the relay to switch a
device, such as a pump,
ON
and
de-energise
the relay to switch the device
OFF
.
Options
Description
0 = Off
Relay is always de-energised
1 = Flow
Relay will
energise
“
ON
” as set in Relay
Setpoint 1
(P2
1
3, 2
2
3). And turns “
OFF
”,
de-energises
, as set in Relay
Setpoint 2
(P2
1
4, 2
2
4).
2 = Velocity
Relay will
energise
“
ON
” as set in Relay
Setpoint 1
(P2
1
3, 2
2
3). And turns “
OFF
”,
de-energises
, as set in Relay
Setpoint 2
(P2
1
4, 2
2
4).
Important Information
A control relay is started and stopped at the “ON” and “OFF” setpoints. To
control down
(reduce level) then set “ON” higher than “OFF”. To
control up
(increase level) then set “ON” lower than “OFF”. For relay 1 “ON” is P213,
“OFF” is P214 and for relay 2 “ON” is P223, “OFF” is P224
The
fourth parameter
, and
fifth parameter
, are set to determine the switch
points, “
ON
” and “
OFF
” for the relay. See
control function
, table (
P211,
221, 231
) for further information.
P213, P223 - Relay Setpoint 1
This parameter determines the “ON” point for the control relay.
Relay Setpoints are entered in values of Measurement Units (P802).
P214, P224 - Relay Setpoint 2
This parameter determines the “OFF” point for the control relay.
Relay Setpoints are entered in values of Measurement Units (P802).
Summary of Contents for Flow Monitor
Page 1: ...Flow Monitor INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 10: ...Page 4 EU Declaration of Conformity...
Page 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Page 26: ...Page 20 This page left blank intentionally...
Page 61: ...Page 55...