Page
40
P804 Time Unit
The value of this parameter determines the time unit of flow and velocity
readings.
Option
Description
1 = per second (Default)
Display flow per second
2 = per minute
Display flow per minute
3 = per hour
Display flow per hour
4 = per day
Display flow per day
P805 Display Offset
The reading is added by the value of this parameter before being displayed.
Default = 0
P806 Display Conversion
The reading is multiplied by the value of this parameter before being
displayed.
Default = 1.0
Failsafe
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display and the output are
held at their last
known
values until a valid reading is obtained.
If required, you can change this so that the unit goes to
high
(max
flow/velocity,
P683
), or
low
(min flow/velocity,
P682
) as follows:
Option
Description
1 = Known (Default)
Remain at the last
known
value
2 = High
Will fail to the
high
value
3 = Low
Will fail to the
low
value
See Also P840 Output Fail-safe
Important Information
In the event of a
fail-safe
condition occurring, the display and Output can be
configured to fail to a condition which is independent of each other. To set
independent
Output Failsafe
see
P840.
Summary of Contents for Flow Monitor
Page 1: ...Flow Monitor INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 10: ...Page 4 EU Declaration of Conformity...
Page 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Page 26: ...Page 20 This page left blank intentionally...
Page 61: ...Page 55...