Installation Instructions
Document No. 570-111
February 18, 2013
Operator Display Panel II (ODP II)
Item No. 570-111. Rev. AA
Page 1 of 4
Product Description
These instructions explain how to field install or
replace the BACnet Fume Hood Controller FHC.
The Fume Hood Controller Operator Display Panel
(ODP) is the interface between the fume hood
operator and the controller system. The mounting
plate is designed for the fume hoods with or without
existing cutouts.
Designed for wall-mounting (A). A conduit box
is optional.
Base plate (B) has screw holes for all
commercially available conduit boxes. The
height of the screw heads must not exceed 3
mm.
Device (C) incorporates a plug, an LCD panel,
emergency purge and horn silence buttons.
Product Number
575-820A
Required Tools
For fume hood with an existing cutout, you need:
Medium Phillips-head screwdriver
For fume hood without a cutout, you need:
Medium duty electric drill
1-1/2 inch (38 mm) hole saw bit
Prerequisites
Cable from controller to ODP is in place.
Cable from controller to ODP is less then 50 feet
(15 m) in length.