ULTRA 3
INSTRUCTION MANUAL
82
To program the Ultra 3 for
Example 1 V-Notch Weir
by using the
Quick
Setup
menu proceed as follows. If required access the
Program Mode
, key
in the
passcode
1997 and press
ENTER
Using the ‘right’ arrow key, go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
Programming is now complete, and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the Flow Oracle 160 will return to
Run Mode
.
QUESTION
OPTION
PMD Type
1 = Exponent
Exponent
6 = V-Notch
Calculation
2 = Ratiometric
No. of alarms
0 = No alarms
Xducer
1 = dB Mach3
Volume units
1 = Litres
Time units
1 = Per second
Measurement units
1 = metres
Empty Level
1.00 metres
Minimum head
0.00 metres
Maximum head
0.40 metres
Totaliser enable
1 = On
Totaliser (R)
0 = No
Totaliser multiplier
7 = 1,000
Max flow
96.5