![Pulsar Measurement Ultra 3 Instruction Manual Download Page 125](http://html1.mh-extra.com/html/pulsar-measurement/ultra-3/ultra-3_instruction-manual_1625418125.webp)
PULSAR MEASUREMENT
125
The
third parameter
has
no function
when
miscellaneous relay
is chosen
and will not be displayed.
The
fourth parameter
, and
fifth parameter
, are set to determine the switch
points, “
ON
” and “
OFF
” for the relay. See
miscellaneous
function table
(
P211, 221, 231
) for further information.
P210, 220, 230, 240, 250 = 1 (Clock)
P213, 223, 233
–
Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at
which relay will energise. Default =
00:00
(
HH:MM
)
P214, 224, 234
–
Relay Setpoint 2
Relay Setpoints are entered in seconds to set the
Time Period
that the relay
will remain ‘ON’.
Default = 0.00 mins.
P210, 220, 230= 2 (Totaliser)
P213, 223, 233
–
Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on-board totaliser
(P820) should be multiplied by to provide a relay closure.
Default = 0.00
P214, 224, 234
–
Relay Setpoint 2
Relay Setpoints are entered in seconds to set the
Time Period
that the relay
will remain ‘ON’.
Default = 0.00 secs.