PULSAR MEASUREMENT
123
The
third parameter
for each relay determines the
assignment
or
condition
of the relay, where required.
P212, P222, P232 - Relay Alarm ID/Pump Group,
P211, 221, 231 = 1 (Time)
This parameter has no function and will not be displayed.
P211, 221, 231 = 2 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Close
condition
(decrease level).
The
fourth parameter
,
fifth parameter
and
sixth parameter
are set to
determine the switch points, “
ON”
and “
OFF
” for the relay and where
required the order of start. See
control function
, table (
P211, 221, 231
) for
further information.
P211, 221, 231 =1 (Time)
P213, P223, P233 - Relay Setpoint 1
This pa
rameter determines the “
Time Period
” that the relay will remain
“
ON
”.
Relay Setpoints are entered in Minutes.
P214, P224, P234 - Relay Setpoint 2
This parameter determines the “
Cycle Time
” for the operation of the relay.
Relay Setpoints are entered in Minutes.
See the appropriate relay function tables (
P211, 221, 231
) for further
information.
P211, 221, 231 = 2 (Step Time)
P213, P223, P233 - Relay Setpoint 1
This parameter will determine the “level” at which the relay will become
active. Relay Setpoint 1 is entered in values of Measurement Units (P104)
P214, P224, P234 - Relay Setpoint 2
Relay Setpoints are entered in Seconds to set Drive Period, the time that the
relay will remain ON.