135
OCM Parameters
When Ultra Wizard = 3 Flow
PMD Setup
P700 Primary Measuring Device Type
This parameter is used to select the
type
of
Primary Measuring Device
and
enable additional parameters required to calculate the flow of the Primary
Measuring Device chosen (P701). Options are as follows:
0 = Off (Default)
1 = Exponent
2 = BS3680 Flume
3 = BS3680 Weir
4 = Not Available
5 = Special
6 = Universal
P701 Primary Measuring Device
Enter the Primary Measuring Device used.
If P700 = 1 (Exponent)
Select from the following options:
1 = Suppressed Rectangular Weir
2 = Cipolletti (Trapezoidal) Weir
3 = Venturi Flume
4 = Parshall Flume
5 = Leopold Lagco Flume
6 = V- notch Weir
7 = Others
8 = Rectangular Weir with End Contractions