PARAMETER
DEFAULT
DESCRIPTION
P101
Transducer
1 = dB Mach3
Type of transducer being used
P706
Volume units
1 = Litres
Units of flow as on display and used for
calculations.
1 = Litres 2 = Cubic metres
3 = Cubic Feet 4 = UK gallons
5 = US gallons 6 = Mil. USG
P707
Time Units
6m
Units of time that volume units will be
displayed and calculated in
P104
Measurement units
1 = Metres
Used to enter dimensions and displayed
where appropriate
1 = Metres 2 = Centimetres
3 = Millimetres 4 = Feet
5 = Inches
P105
Empty Level
2.425m
Distance from the end of the transducer
horn (dB Mach3) or face of the
transducer to the material at the
bottom of the measuring element
P703
Minimum head
0.00m
Distance from empty point (P105) to
zero flow.
P704
Max head
2.425m
Distance from zero flow to max flow. It
should be noted that any change to
P704 updates P106 Span and vice versa.
P824
Totaliser enable
1 = On
Enables the flow totaliser, P820, options
are
0
=
Off
,
1
=
On
. Note this totaliser can
be viewed during run via the totaliser
“Hot Key” It can be reset but only
via
P820, whilst in “program mode”.
P816
Totaliser (R)
0 = No
Enables the totaliser to be displayed in
the auxiliary display whilst in “run
mode”. Note the totaliser is “resettable”
whilst in run mode via the totaliser hot
key.