PULSAR MEASUREMENT
115
OPTION
DESCRIPTION
SETPOINTS
5 = LoLo
Same as 4 = Lo, but
different identifier
6 = In bounds
Relay goes “ON” if value is
inside the zone between
the two setpoints.
Relay Setpoints, P2
1
3,
2
2
3, 2
3
3 and P2
1
4, 2
2
4,
2
3
4 can be set in any
order as the unit
‘knows’
that you are setting an
inbounds alarm.
7 = Out of bounds
Relay goes “ON” if value is
outside the zone between
the two setpoints.
Relay Setpoints P21
3
,
2
2
3, 2
3
3 and P2
1
4, 2
2
4,
2
3
4 can be set in any
order as the unit ‘knows’
that you are setting an
out of bounds alarm.
The
fourth parameter
and the
fifth parameter
for each relay set the
Alarm
“
ON
” and “
OFF
” points. For a
high alarm,
the “
ON
” is set
higher than
“
OFF
”.
For
low
alarm,
then “
ON
” is set
lower than
“
OFF
”. See the appropriate
alarm
ID,
table (
P212, 222, 232
) for further information.
When P211, 221, 231 = 4 (L0ss of Echo) or 5 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, 221, 231 = 1 (Level), 2 (Rate of Change)
or
3 (Temperature)
P213, P223, P233 - Relay Setpoint 1
Determines the “ON” or “OFF” point for the alarm according to the ID
selected.
P214, P224, P234 - Relay Setpoint 2
Determines the “ON” or “OFF” point for the alarm according to the
ID
selected.