To program the Ultra 3 for
Example 1 Level Monitoring with Alarms
by
using the Quick Setup
menu proceed as follows. If required to access
Program Mode,
key in the
passcode
1997
and press
ENTER
At the
Quick Setup
menu press
ENTER
and as prompted, by the questions,
select the relevant option and
ENTER
.
QUESTION
OPTION
Level/Pump up or down
1 = Level App.
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 1
Type alarm 2
2 = Low
Alarm no.2
2 = Set relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the Ultra 3 will return to the
Run Mode
.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either
by the main menu system or directly via parameter number and changed
as necessary.