23
5. Setting the display
Menu-level
Parameter-level
Limit values,
LI-1:
Default:
0200
The limit value specifies the threshold above which the alarm reacts or is activated /
deactivated.
Hysteresis for limit values,
HY-1:
Default:
0000
The hysteresis defines a difference to the limit value by which an alarm reacts delayed.
Function for undercutting/exceeding the limit value,
FU-1
:
Default:
hi9h
The limit value violation is selected with
Louu
(for LOW = lower limit value) and that with
HiGH
(for HIGH = upper limit value). Derived from "lower limit" = lower limit value and higher limit =
upper limit value. If, for example, limit value 1 is set to a switching threshold of 100 and
assigned the function high, the alarm is activated when the switching threshold is reached. If
the limit value is assigned to
Low
an alarm is triggered when the value falls below the switching
threshold, as long as the hysteresis is zero.
Limit values,
LI-2
:
Default:
0300
The limit value specifies the threshold above which the alarm reacts or is activated /
deactivated.
Hysteresis for limit values,
HY-2
:
Default:
0000
The hysteresis defines a difference to the limit value by which an alarm reacts delayed.